Tyco Fire Protection Products showcased its experience in water mist suppression options on the International Water Mist Association (IWMA) Conference in Istanbul. Dr Tim Nichols, Sales Director Water Mist EMEA, gave a presentation entitled ‘Fire Protection of Compact Archive Storage using Water Mist’, the place he mentioned how the extinguishant is well suited to the protection of irreplaceable works and artefacts in highly priceless buildings.
Tim’s lecture centered on a hearth check protocol that was formulated to confirm the efficiency and use of Tyco’s own water mist resolution, AquaMist, in an historic building, residence to valuable archive storage. The National Fire Protection Association (NFPA) 750 standard requires that, when employing a water mist suppression system, fireplace testing is undertaken pertinent to the risk. However, of the revealed fireplace test protocols listed in NFPA 750, none details the requirements for archives that comprise roller (compact) racking. Many of the racks in the focused building are of the ‘roller’ sort, which restrict the quantity of area for building services, together with these for extinguishing system pipework.
Together with เกจวัดแรงดันคือ , Tyco devised the protocol to incorporate take a look at rig and structure, check type, fireplace load, knowledge acquisition (for instance, sensors and imaging), hardware required (such as pumps, nozzles, pipe, tank, generator), and health and security procedures (for occasion, the fire brigade). The related performance based mostly fireplace checks had been then designed to replicate the range of software parameters related to archive storage.
While ignition sources on the authentic site had been identified to be minimal, and the primary fireplace source confirmed as arson, the multi-level building poses quite a few challenges that had to be considered when formulating the fire test protocol to guarantee efficient safety. Low ceilings and quite a few obstructions, similar to lighting, ducts and pillars, contribute towards the confined setting of the archive storage basement degree. Items are stored in a mix of open racks and compact racks, which supply lower than a 150mm hole between themselves and the ceiling, and there might be restricted on-site water storage. Pre-test risk evaluation additionally highlighted restricted access and exits below and above ground, so it is important for storage space to be maximised and protected egress provided in case of the occasion of a fire. In addition, the extremely priceless nature of the storage contents meant that the selected hearth suppression resolution had to make sure minimal damage to those historical objects.
To achieve validation, the checks needed to meet numerous objectives. These comprised rapid control of the hearth within a prescribed area (in this case, outlined as within a block of racks); control of temperature; attenuation of radiation; and minimisation of collateral injury via water clean-up. They also had to take into account numerous parameters, including the required high pressure mist system; a 30 minute run time; and an annual measurable achievement goal (AMAO) defined according to a formulation based on the quantity of nozzles activating throughout testing.
The hearth checks, carried out for both open and curler racks with minimal storage gaps, were undertaken in a customised take a look at rig, designed, constructed and fitted to duplicate the exact specification, racking preparations and storage supplies of the location. Considered a high load, the fuel materials had been equivalent to that present in archive storage, including paper, books, micro-film and CD instances.
Success was defined by cross or fail standards and decided by detailed quantitative measurements on system configuration, hydraulic analysis, discharge stress, discharge sequence, hearth unfold, temperature, hearth injury and water consumption. In both checks, Tyco’s AquaMist system operated successfully and was noticed to suppress and control the fireplace effectively. The project team was impressed by the dearth of fireside and smoke injury to the supplies and structure and the product has since been put in within the constructing in question.
“The IWMA convention is a unbelievable alternative to focus on the benefits of water mist as a hearth suppression solution, as well as show its versatility in a wide range of functions,” feedback Dr Tim Nichols. “Identifying a gap out there and taking the opportunity to formulate a fire take a look at protocol for archive storage enabled us to validate the professional capabilities of our AquaMist system and facilitate safety of a customer’s extremely priceless assets.”
For more info, go to www.tfppemea.com